Baseline case
Illustrative defaults under the expected scenario, not a recommended design or verified farm.
Inputs
- Floor area1,800 m²
- Inside-outside ΔT25 °C
- Envelope U-value0.5 W/m²·K
- Minimum ventilation1.2 m³/h per m²
- Brooder capacity40,000 BTU/hr
- Burner efficiency90 %
- Equivalent full-load hours10 h/day
- LPG price0.9 USD/kg
Results
- Envelope loss22.5 kW
- Ventilation loss17.8 kW
- Total heat load40.3 kW
- Peak BTU/hr137572