Poultry generator sizing calculator: full guide

This guide explains what the poultry generator sizing calculator computes, how each input changes the result, and how to turn the output into a comparable request for quotation. Worked examples below are produced with the same engine that powers the live tool.

Open the calculator

How to use this calculator

  1. 1

    Enter your project figures

    Defaults are illustrative model inputs, not verified industry averages. Replace them with your records, dated quotes and professionally reviewed assumptions.

  2. 2

    Compare the three scenarios

    Switch between conservative, expected and optimistic to see how sensitive the result is to your assumptions before committing capital.

  3. 3

    Read the assumptions

    Check the assumptions panel so you know what the model excludes — typically taxes, import duties, special civil works and land.

  4. 4

    Turn the output into a quote request

    Put the figures into one written project request. Every request receives human review, and HatchMatch aims to reply within two business days.

Every input explained

Defaults are illustrative model inputs, not verified industry averages. Replace them with your records, dated quotes and professionally reviewed assumptions.

Total running load (kW)
103
Largest motor (direct-on-line) (kW)
11
Critical load to keep alive (kW)
20
Generator power factor
0.8
Supply voltage (line-to-line) (V)
400
Phases (1 or 3)
Farm supplies are single- or three-phase. A US split-phase 120/240 V ("2-wire" or "2-phase") supply is single-phase: choose 1 and enter 240 V. — 3
Diesel tank size (L)
1,000
Battery autonomy (h)
1

Worked examples

Three illustrative model scenarios, computed with the calculator engine; not observed farms or promised outcomes.

Baseline case

Illustrative defaults under the expected scenario, not a recommended design or verified farm.

Inputs

  • Total running load103 kW
  • Largest motor (direct-on-line)11 kW
  • Critical load to keep alive20 kW
  • Generator power factor0.8
  • Supply voltage (line-to-line)400 V
  • Phases (1 or 3)3
  • Diesel tank size1,000 L
  • Battery autonomy1 h

Results

  • Standby generator size197 kVA
  • Diesel runtime on full tank40.8 h
  • Battery bank (nominal)23.6 kWh
  • ATS frame400 A

Scale-up case

Selected capacity-related inputs increased by up to 2.5× within field limits; check every input shown.

Inputs

  • Total running load103 kW
  • Largest motor (direct-on-line)11 kW
  • Critical load to keep alive20 kW
  • Generator power factor0.8
  • Supply voltage (line-to-line)400 V
  • Phases (1 or 3)3
  • Diesel tank size1,000 L
  • Battery autonomy1 h

Results

  • Standby generator size197 kVA
  • Diesel runtime on full tank40.8 h
  • Battery bank (nominal)23.6 kWh
  • ATS frame400 A

Conservative case

The same inputs under the engine’s conservative scenario; not a statistical confidence interval.

Inputs

  • Total running load103 kW
  • Largest motor (direct-on-line)11 kW
  • Critical load to keep alive20 kW
  • Generator power factor0.8
  • Supply voltage (line-to-line)400 V
  • Phases (1 or 3)3
  • Diesel tank size1,000 L
  • Battery autonomy1 h

Results

  • Standby generator size259 kVA
  • Diesel runtime on full tank34.7 h
  • Battery bank (nominal)23.6 kWh
  • ATS frame630 A

Planning assumptions

  • The poultry generator sizing calculator uses illustrative model inputs unless its methodology identifies a source; replace them with measured records and reviewed assumptions.
  • Scenario labels describe model assumptions, not probabilities, verified improvements or guaranteed safety margins.
  • Taxes, import duties, special civil works and land cost are excluded unless stated otherwise.